CT Zone Pack DN20 (Constant Temperature)

Comprises: High Efficiency pump options, isolation ball valves, temperature gauges and non-return valve. Available in ¾” BSP connections. Supplied with insulation box cover. Specification of CT Pack:

Pipework Supply:

¾” Union Connection.

Union Flanged Ball Valve with T-handle, for Pump Isolation & Removal.

Synchronous pre-wired Wilo Circulating Pump with cable 2 m. long (6mtr or 8 mtr options)

Union Flanged Ball Valve with Thermometer ‘handle’ (coded red, range 0°C-120°C).

 

Pipework Return:

¾” Union Connection.

Union Flanged Ball Valve with Thermometer ‘handle’ (coded blue; 0°C-120°C) and non-return valve 20 mbar

 

Centre distance: 90 mm. Insulation Box Measurements: 180x302x142 mm.

 

Max Temperature: 110°C (unit without pump).

 

Connections: 3/4” Male Union to the Modvlvs Piping Distributor.

 

Constant Temperature Pump Pack Codes: CT20255R-C6 & CT-20255R-C8

 

Zone Applications: Each Pack up to 35 kW (with Δt 20 c) and maximum flow 1500 l/h, Kvs value 6.0

 

Approximate data calculated with a 6 mtr circulating pump. For specific applications and higher flowrates, please refer to the Pump Curves available.